Title The ways of making the power transformer’s transformation coefficient more precise /
Another Title Patikslintas galios transformatoriaus transformacijos koeficiento nustatymas.
Authors Kairys, A ; Kostrauskas, P
Full Text Download
Is Part of Elektronika ir elektrotechnika.. Kaunas : Technologija. 2004, Nr. 6, p. 58-61.. ISSN 1392-1215. eISSN 2029-5731
Abstract [eng] Presented the method of determination transformation coefficient of power transformer, when known distance between primary and secondary windings. Given dependency between magnetic fluxes and no-load voltages. Transformation coefficients are express as functions of magnetic fluxes (main and leakage) and no-load voltages. Formulas are received with estimation of magnetic leakage fluxes for calculation of the number turn windings of multi-wound transformer under given turn ratio with inaccuracy not exceeding ±0,5%. Presented physical model of multi-wound power transformer, which allow calculate a number of turns of secondary windings for defined transformation coefficient. The Results of the work can be used when designing power multi-wound transformer with specifically exact transformation coefficient.
Published Kaunas : Technologija
Type Journal article
Language English
Publication date 2004
CC license CC license description